Loading…
Name ID Label Description Type Access Class
device_specific_status_15 1032 Status Group 15 Field Device Specific Status Byte 16- Data that has Field Device status information relating to: failures / warnings / status of process's. R BitEnum 2051
device_specific_status_16 1033 Status Group 16 Field Device Specific Status Byte 17- Data that has Field Device status information relating to: failures / warnings / status of process's. R BitEnum 2051
device_specific_status_17 1034 Status Group 17 Field Device Specific Status Byte 18- Data that has Field Device status information relating to: failures / warnings / status of process's. R BitEnum 2051
device_specific_status_18 1035 Status Group 18 Field Device Specific Status Byte 19- Data that has Field Device status information relating to: failures / warnings / status of process's. R BitEnum 2051
loopCurrent 00ED Loop current Loop Current- Loop current value as perceived by the device. R Float 66
loop_alarm_code 00EC AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R Enum 64
loop_flags 00E7 Channel flags Analog Channel Flags- Defines the characteristics of the Analog Channel R BitEnum 64
percentRange 00E9 PV % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
transfer_function 1F84 Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R Enum 32
upperRange_value 00EA PV URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
Name ID Label Description Type Access Class