Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
extsw | 400B | ExtSw mode | R/W | Enum | 2048 | |
si_unit | 400C | SI Unit | R/W | Enum | 2048 | |
alarm_state | 400D | Alarm Status | Alarm Status- Displays the current alarm output status. | R | BitEnum | 35 |
co_state | 400E | Contact Output Status | Contact Output Status- Displays the status of the contact output. --Open: The contact output circuit is open. --Closed: The contact output circuit is closed. --Sim Open: The contact output circuit is open in simulation mode. --Sim Closed: The contact output circuit is closed in simulation mode. | R/W | Enum | 34 |
alarm_pv_conf | 4010 | Output Alarm | Output Alarm- Configures the output alarm. --No Alarm: Output alarm is not used. --Low Limit: If the output is below the low limit for the output alarm, the alarm is activated. --High Limit: If the output is above the high limit for the output alarm, the alarm is activated. --Low/High Limit: If the output is either below the low limit or above the high limit for the output alarm, the alarm is activated. | R/W | Enum | 2048 |
alarm_pv_low | 4011 | Output Alarm Low Limit | Output Alarm Low Limit- Sets the low limit for the Output Alarm. | R/W | Float | 2048 |
alarm_pv_high | 4012 | Output Alarm High Limit | Output Alarm High Limit- Sets the high limit for the Output Alarm. | R/W | Float | 2048 |
alarm_temp_conf | 4013 | Sensor Temp. Alarm | Sensor Temp. Alarm- Configures the temperature alarm. --No Alarm: Sensor temperature alarm is not used. --Low Limit: If the sensor temperature is below the low limit for the sensor temperature alarm, the alarm is activated. --High Limit: If the sensor temperature is above the high limit for the sensor temperature alarm, the alarm is activated. --Low/High Limit: If the sensor temperature is either below the low limit or above the high limit for the sensor temperature alarm, the alarm is activated. | R/W | Enum | 2048 |
alarm_temp_low | 4014 | Sensor Temp. Alarm Low Limit | Sensor Temp. Alarm Low Limit- Sets the low limit for the Sensor Temp. Alarm. | R/W | Float | 2048 |
alarm_temp_high | 4015 | Sensor Temp. Alarm High Limit | Sensor Temp. Alarm High Limit- Sets the high limit for the Sensor Temp. Alarm. | R/W | Float | 2048 |
co_type | 4016 | Contact Output Mode | Contact Output Mode- Sets the contact output mode to either Normally Open or Normally Closed. --Normally Open: Contacts are normally open, but close when an alarm is detected. --Normally Closed: Contacts are normally closed, but open when an alarm is detected. | R/W | Enum | 2048 |
alarm_select | 4017 | Contact Output ON/OFF | Contact Output ON/OFF- Selects the alarms to reflect the contact output. | R/W | BitEnum | 2048 |
alarm_select_output_low | 40DD | Output Low | Output Low- This parameter determines whether or not detection of the output low-limit alarm is connected to the contact output circuit. | R/W | Enum | 2048 |
alarm_select_output_high | 40DE | Output High | Output High- This parameter determines whether or not detection of the output high-limit alarm is connected to the contact output circuit. | R/W | Enum | 2048 |
alarm_select_temp_low | 40DF | Sensor Temp. Low | Sensor Temp. Low- This parameter determines whether or not detection of the sensor's low-limit temperature alarm is connected to the contact output circuit. | R/W | Enum | 2048 |
alarm_select_temp_high | 40E0 | Sensor Temp. High | Sensor Temp. High- This parameter determines whether or not detection of the sensor's high-limit temperature alarm is connected to the contact output circuit. | R/W | Enum | 2048 |
alarm_select_dummy | 40E1 | alarm_select_dummy | R | Unsigned | 4096 | |
disp_mode | 4018 | Display Mode | Display Mode- Sets the device indicator's method of display. --%: Displays the currently measured pressure as a percentage of the preset measurement range. --Pressure: Displays the currently measured pressure in the selected pressure unit. --Scale: Displays the measured value (flow rate, level etc.) in user-selected or user-defined units. | R/W | Enum | 256 |
disp_sqrt | 4019 | Display Function | Display Function- Sets the type of analog output from the device. --Linear: Displays PV by linear scale. --Square root: Displays flow by square root extraction. | R/W | Enum | 256 |
disp_unit | 401A | Disp. Unit | Disp. Unit- Selects the engineering unit displayed on the indicator of the device. Valid when Scale is selected for Display Mode. | R/W | Enum | 256 |
disp_exponent | 401B | Exponent | Exponent- Selects the exponent (X10, X100, etc.) displayed on the indicator of the device. Valid when Scale is selected for Display Mode. | R/W | Enum | 256 |
cutoff_mode | 401C | Cutoff Mode | Cutoff Mode- Displays one of the following Cutoff Mode status indications. --Def (7.1%Lin): The default Cutoff Mode is in effect. (Flow mode is the default value, dropout is linear, and cutoff point is 7.1%) --Zero Flow & Dflt: Dropout is zero and flow mode is the default value. --Lin. Flow & Dflt: Dropout is linear and flow mode is the default value --Zero Flow & Bi-dir: Dropout is zero and flow mode is bi-directional. --Lin. Flow & Bi-dir: Dropout is linear and flow mode is bi-directional. --Dropout: Determines behavior below the cutoff value (either zero or linear). --Flow mode: Determines the method of calculating the flow output, either default (square root of positive output) or bi-directional (square root of both positive and negative outputs). | R | Enum | 64 |
dropout_point | 401D | Cutoff Point | Cutoff Point- Displays the cutoff point (%) that is valid when Square Root is selected as the Xfer fnctn. | R/W | Float | 64 |
eu_lower_value | 401E | EULO (0%) | EULO (0%)- The value displayed on the indicator of the device when the output from the device is 0%. Valid when Scale is selected for Display Mode. | R/W | Float | 256 |
eu_upper_value | 401F | EUHI (100%) | EUHI (100%)- The value displayed on the indicator of the device when the output from the device is 100%. Valid when Scale is selected for Display Mode. | R/W | Float | 256 |
out_lower_limit | 4020 | Output Low Limit | Output Low Limit- Sets the low limit for the Loop current. | R/W | Float | 64 |
out_upper_limit | 4022 | Output High Limit | Output High Limit- Sets the high limit for the Loop current. | R/W | Float | 64 |
type_code | 4023 | Measurement Type | Measurement Type- Displays the device's sensor type. --DP: Differential pressure --GP: Gauge pressure --AP: Absolute pressure | R/W | Enum | 2048 |
prom_id | 4024 | PROM No. | PROM No.- Displays PROM No. used for the device. | R | ASCII | 2048 |
conf_de_type | 4025 | SFN Communicator | R/W | Enum | 2048 | |
userunit | 4026 | User Unit | User Unit- Sets the user-defined unit displayed on the indicator of the device. Valid when Scale is selected for Display Mode. | R/W | ASCII | 256 |
status_record_0 | 4027 | Status Record 0 | R | BitEnum | 2049 | |
status_record_1 | 4028 | Status Record 1 | R | BitEnum | 2049 | |
status_record_2 | 4029 | Status Record 2 | R | BitEnum | 2049 | |
status_record_3 | 402A | Status Record 3 | R | BitEnum | 2049 | |
zero_correct1 | 402B | 1 (Latest) | 1 (Latest)- Displays the zero corrected value as a percentage of the Upper Range Limit. | R | Float | 2048 |
zero_correct2 | 402C | 2 | 2- Displays the zero corrected value as a percentage of the Upper Range Limit. | R | Float | 2048 |
zero_correct3 | 402D | 3 | 3- Displays the zero corrected value as a percentage of the Upper Range Limit. | R | Float | 2048 |
zero_correct4 | 402E | 4 | 4- Displays the zero corrected value as a percentage of the Upper Range Limit. | R | Float | 2048 |
zero_correct5 | 402F | 5 | 5- Displays the zero corrected value as a percentage of the Upper Range Limit. | R | Float | 2048 |
zero_correct_current | 4030 | Zero Correct Current | R | Float | 2048 | |
zero_correct_count | 4031 | Count | R | Integer | 2048 | |
sw_write_protect | 4032 | Software Write Protect | Software Write Protect- Displays the status of software write protection. | R/W | Enum | 2048 |
hw_write_protect | 4033 | Hardware Write Protect | Hardware Write Protect- Displays the status of hardware write protection. | R | Enum | 2048 |
analog_output_conf | 4021 | Analog Output Configuration | R | Enum | 2048 | |
hardware_equipment | 400F | Hardware Equipment | R/W | BitEnum | 2048 | |
fw_sw_version | 4034 | Software Version | R | Unsigned | 2048 | |
height | 40B4 | Height | Height- Compensates for the effects of temperature change on the fill fluid of the remote sealed transmitter. User must enter the distance between the flanges in order to use this compensation. | R/W | Float | 32 |
set_output_value | 4035 | Set Output Value | R/W | Float | 4096 | |
set_burnout_sim | 40B5 | Burnout Simulation | R/W | Enum | 4096 | |
Name | ID | Label | Description | Type | Access | Class |