Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
alarm_select | 4017 | Contact Output ON/OFF | Contact Output ON/OFF- Selects the alarms to reflect the contact output. | R/W | BitEnum | 2048 |
disp_mode | 4018 | Display Mode | Display Mode- Sets the displayed units for the device indicator. --%: Displays the currently measured pressure as a percentage of the preset measuring range. --Pressure: Displays the currently measured pressure in the selected pressure unit. --Scale: Displays the measured value in user-selected or user-defined units (flow rate, level etc.) | R/W | Enum | 256 |
disp_sqrt | 4019 | Display Function | Display Function- Sets the display conformity of device. --Linear: Displays PV by linear scale. --Square root: Displays flow (square root extraction). | R/W | Enum | 256 |
disp_unit | 401A | Disp. Unit | Disp. Unit- Selects engineering unit displayed in the indicator of device. Valid when Scale is selected in Display Mode. | R/W | Enum | 256 |
disp_exponent | 401B | Exponent | Exponent- Selects the exponent(X10, X100, etc) displayed in the indicator of device. Valid when Scale is the selected in Display Mode. | R/W | Enum | 256 |
cutoff_mode | 401C | Cutoff Mode | Cutoff Mode- Displays the status of Cutoff mode. --Def (7.1%Lin): Cutoff mode is default. (Flow mode is default, dropout is linear, and cutoff point is 7.1%) --Zero Flow:Def: Dropout is zero, and flow mode is default. --Lin. Flow:Def: Dropout is linear, and flow mode is default --Zero Flow:Bi-dir: Dropout is zero, and flow mode is bi-directional. --Lin. Flow:Bi-dir: Dropout is linear, and flow mode is bi-directional. --Dropout: Selects behavior below the cutoff value. Selects either zero or linear. --Flow mode: Selects calculation method of flow output.Selects either default (square root of positive output) or bi-direction (square root of both positive and negative outputs.) | R | Enum | 64 |
dropout_point | 401D | Cutoff Point | Cutoff Point- Displays the cutoff point (%) valid when Transfer function is the selected Square Root. | R/W | Float | 64 |
eu_lower_value | 401E | EULO (0%) | EULO (0%)- The value displayed in the indicator of device when the output of the device is 0%. Valid when Scale is selected in Display Mode. | R/W | Float | 256 |
eu_upper_value | 401F | EUHI (100%) | EUHI (100%)- The value displayed in the indicator of device when the output of the device is 100%. Valid when Scale is selected in Display Mode. | R/W | Float | 256 |
out_lower_limit | 4020 | Output Low Limit | Output Low Limit- The output limit of Lower value (0%). | R/W | Float | 64 |
Name | ID | Label | Description | Type | Access | Class |