Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
pressureValue | 4062 | Pres | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 10 |
pressureUnits | 4063 | Pressure unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. Pressure- Pressure of the process measured with respect to a reference pressure | R/W | Enum | 0 |
pressureFamily | 4064 | Pres Dev fmly | Device Family- Indicates the family (i.e, pressure, temperature, flow, etc.) that the device variable belongs. | R | Enum | 2048 |
pressureClassification | 4065 | Pres Class | Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. | R | Enum | 0 |
pressurePDQ | 4066 | Pres PDQ | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 10 |
pressureLS | 4067 | Pres LS | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 10 |
pressureStatus | 4068 | Pres Fmly stat | Device Family Status- Indicates additional status information on a device variable for a specific device family. | R | BitEnum | 10 |
pressureUSL | 4069 | Pres USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 0 |
pressureLSL | 406A | Pres LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 0 |
pressureMinimumSpan | 406B | Pres min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 0 |
pressureDampingValue | 406C | Pres damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Float | 0 |
pressureUpdatePeriod | 4094 | Pressure Update Period | R | Time | 0 | |
pressureSerialNumber | 406E | Pres snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 2048 |
pressureLowerTrimPoint | 406F | Pres Lower trim | Lower Trim Point- Applied process input at which the last lower trim of the device variable was performed. | R | Float | 0 |
pressureUpperTrimPoint | 4070 | Pres Upper trim | Upper Trim Point- Applied process input at which the last upper trim of the device variable was performed. | R | Float | 0 |
pressureTrimSupport | 4071 | Pres Trim support | Trim Points Supported- Indicates the trim points that are supported by the device variable during a trim procedure. | R | Enum | 0 |
pressureMinimumLTP | 4072 | Pres Min lower trim | Minimum Lower Trim Point- The lowest applied process value that can be used duirng a low trim procedure (ie, no value lower than this will be accepted by the instrument). | R | Float | 0 |
pressureMaximumLTP | 4073 | Pres Max lower trim | Maximum Lower Trim Point- The highest applied process value that can be used duirng a low trim procedure (ie, no value higher than this will be accepted by the instrument). | R | Float | 0 |
pressureMinimumUTP | 4074 | Pres Min upper trim | Minimum Upper Trim Point- The lowest applied process value that can be used duirng a high trim procedure (ie, no value lower than this will be accepted by the instrument). | R | Float | 0 |
pressureMaximumUTP | 4075 | Pres Max upper trim | Maximum Upper Trim Point- The highest applied process value that can be used duirng a high trim procedure (ie, no value higher than this will be accepted by the instrument). | R | Float | 0 |
pressureMinimumTrimDiff | 4076 | Pres Min trim diff | Minimum Trim Differential- The minimum acceptable difference between the upper and lower trim points. | R | Float | 0 |
pressureSimulated | 4077 | Simulate | W | Enum | 2052 | |
temperatureValue | 4079 | Snsr temp | Sensor Temperature- Temperature of the sensor that is making the process measurement | R | Float | 10 |
temperatureUnits | 407A | Snsr temp unit | Sensor Temperature Units- Engineering unit to be displayed with Sensor Temperature. | R/W | Enum | 8 |
temperatureFamily | 407B | Device family | R | Enum | 2048 | |
temperatureClassification | 407C | Temp Class | R | Enum | 0 | |
temperaturePDQ | 407D | Temp PDQ | R | Enum | 10 | |
temperatureLS | 407E | Temp LS | R | Enum | 10 | |
temperatureStatus | 407F | Temp Dev Stat | R | BitEnum | 10 | |
temperatureUSL | 4080 | Temp USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 0 |
temperatureLSL | 4081 | Temp LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 0 |
temperatureMinimumSpan | 4082 | Temp min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 0 |
temperatureDampingValue | 4083 | Temp damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R | Float | 0 |
temperatureUpdatePeriod | 4095 | Temp Update Period | R | Time | 0 | |
temperatureSerialNumber | 4085 | Temp snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 2048 |
temperatureSimulated | 4086 | Simulate | W | Enum | 2052 | |
point_position | 4016 | Trim Mode | Select trim mode | R/W | Enum | 8 |
current_value | 4018 | Current trim value | Current PV value | R/W | Float | 2048 |
apply_value | 4019 | Apply trim value | Change current value to apply value for trim | R/W | Float | 2048 |
Dev_Xmtr_Var_Code | 401B | Xmtr Variable | Device transmitter variable code | W | Enum | 8 |
apt_3200_Sen_Type_Code | 404A | Selected Sensor Type | Pressure Tranmitter Sensor Type Code | R | Enum | 8 |
lcd_display_mode | 401E | LCD Display Mode | LCD mode | R/W | Enum | 8 |
eng_xfer_ftn | 4048 | Engr. Xfer Fnctn | R/W | Enum | 8 | |
decimal_place | 404B | Decimal Place | R/W | Enum | 8 | |
eng_range_unit | 4043 | Engr. Range Unit | R/W | Enum | 8 | |
eng_lower_range | 4046 | Engr. LRV | R/W | Float | 2048 | |
eng_upper_range | 4047 | Engr. URV | R/W | Float | 2048 | |
eng_user_defined_unit | 4060 | User Defined unit | R/W | ASCII | 2048 | |
zero_adjust_value | 4050 | Adjust value | Change current PV to zero adjustmet value | R/W | Float | 2048 |
adjust_division | 4061 | Adjust Mode | Select Zero Adjust mode | R/W | Enum | 8 |
Name | ID | Label | Description | Type | Access | Class |