Loading…
Name ID Label Description Type Access Class
analog_value 4013 AO Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes R/W Float 66
analog_alarm_code 4014 AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R Enum 64
analog_damping_value 402E AO1 Added damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 10
analog_units 402F Anlog unit R Enum 64
analog_upper_endpoint_value 4030 AO1 Hi end pt R Float 8
analog_lower_endpoint_value 4031 AO1 Lo end pt R Float 8
input_percent_range 4032 PV % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
input_transfer_function 4033 Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R/W Enum 32
input_units 4034 PV rnge unit Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value R Enum 32
input_upper_value 4035 PV URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
Name ID Label Description Type Access Class