Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
current_lower_trim_point | 4000 | Lower current trim point | Lower current trim point | R | Float | 8 |
current_upper_trim_point | 4001 | Upper current trim point | Upper current trim point | R | Float | 8 |
sensor_lower_trim_point | 4002 | Lower sensor trim point | Applied process pressure at which the last low sensor trim was performed. | R/W | Float | 8 |
sensor_upper_trim_point | 4003 | Upper sensor trim point | Applied process pressure at which the last upper sensor trim was performed. | R/W | Float | 8 |
current_units | 4004 | Current units | Current units | R | Enum | 8 |
kind_of_trim | 4005 | Kind of trim | User calibrations (sensor calibrations) are replaced by the original factory calibrations. | W | Enum | 32 |
product_code | 4006 | Product code | Product code as generated from the product catalogue. It is related to the pressure trasmitter and its optional. A modification of the product code will not affect device functionally. | R | ASCII | 2048 |
separator_code | 4007 | Separator code | Product code as generated from the product catalogue. It is related to the Remote Seal connected to the positive side of the transmitter. If no remote seal connected the code is blank. A modification of the product code will not affect device functionally. | R | ASCII | 2048 |
manifold_code | 4008 | Manifold code | Product code as generated from the product catalogue. It is related to the Remote Seal connected to the negative side of the transmitter.If no remote seal connected the code is blank. A modification of the product code will not affect device functionally | R | ASCII | 2048 |
long_tag | 4009 | Long tag | Tag 24 ASCII character | R/W | ASCII | 2048 |
Name | ID | Label | Description | Type | Access | Class |