Loading…
Name ID Label Description Type Access Class
curCmdVal 4004 Current Command Value R Float 10
curCmdUnits 4005 Current Command Unit R Enum 8
curCmdFamily 4006 Device family R Enum 2048
curCmdClassification 4007 Current Command Class R Enum 0
curCmdPDQ 4008 Current Command PDQ R Enum 10
curCmdLS 4009 Current Command LS R Enum 10
curCmdStatus 400A Current Command Stat R BitEnum 10
curCmdUSL 400B Current Command USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 0
curCmdLSL 400C Current Command LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 0
curCmdMinSpan 400D Current Command min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 0
curCmdDampingValue 400E Current Command Damping Value Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 0
curCmdUpdatePeriod 400F Current Command Update Period R Time 0
curCmdSerialNumber 4010 Current Command s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R/W Unsigned 2048
curCmdSimulated 4011 Current Command Simulate W Enum 2052
fbVal 4013 Feedback Value R Float 10
fbUnits 4014 Feedback Unit R Enum 8
fbFamily 4015 Device family R Enum 2048
fbClassification 4016 Feedback Class R Enum 0
fbPDQ 4017 Feedback PDQ R Enum 10
fbLS 4018 Feedback LS R Enum 10
fbStatus 4019 Feedback Stat R BitEnum 10
fbUSL 401A Feedback USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 0
fbLSL 401B Feedback LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 0
fbMinSpan 401C Feedback min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 0
fbDampingValue 401D Feedback Damping Value Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 0
Name ID Label Description Type Access Class