Loading…
Name ID Label Description Type Access Class
uepSV 40A8 AO hi end pt Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
lepSV 40A9 AO lo end pt Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
ulvSV 40AA Upper Limit Value The maximum value of the analog signal. R Float 64
llvSV 40AB Lower Limit Value The minimum value of the analog signal. R Float 64
adpSV 40AC Added damp Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R Float 64
acfSV 40AD Channel flags Analog Channel Flags- Defines the characteristics of the Analog Channel R BitEnum 64
pcrTV 40B0 TV % range Percent of range of the HART Secondary Variable (SV); tracks the associated measured value with respect to the Lower Range Value and Upper Range Value. R Float 34
tfcTV 40B1 Xfer fnctn R Enum 32
urvTV 40B2 URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
lrvTV 40B3 LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
Name ID Label Description Type Access Class