Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
relayPDQ | 4045 | Relay PDQ | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 10 |
relayLS | 4046 | Relay LS | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 10 |
relayStatus | 4047 | Relay Fmly stat | Device Family Status- Indicates additional status information on a device variable for a specific device family. | R | BitEnum | 10 |
relayUSL | 4048 | Relay USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 0 |
relayLSL | 4049 | Relay LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 0 |
relayMinimumSpan | 404A | Relay min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 0 |
relayDampingValue | 404B | Relay Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R | Float | 0 |
relaySerialNumber | 404C | Relay snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 2048 |
relayLowerTrimPoint | 404D | Relay Lower trim | Lower Trim Point- Applied process input at which the last lower trim of the device variable was performed. | R | Float | 0 |
relayUpperTrimPoint | 404E | Relay Upper trim | Upper Trim Point- Applied process input at which the last upper trim of the device variable was performed. | R | Float | 0 |