Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
damping_value_S2 | 40D4 | Damping | Damping time constant applied to both the Digital Value representation and Analog Value of a respective Analog Output. The units of this variable are always in seconds | R/W | Float | 0 |
sensor2_upper_sensor_limit | 402A | Upper Limit | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 0 |
sensor2_lower_sensor_limit | 4029 | Lower Limit | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 0 |
sensor2_minimum_span | 402B | Min Span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 0 |
snr2qty | 40D5 | Sensor 2 Status | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 2 |
sensor2_trim_unit | 404D | sensor2 trim low | R/W | Enum | 0 | |
sensor2_trim_low | 404E | sensor2 trim low | R/W | Float | 0 | |
sensor2_trim_high | 404F | sensor2 trim high | R/W | Float | 0 | |
sensor2_trim_support | 4050 | Sensor2 trim support | Trim Points Supported- Indicates the trim points that are supported by the device variable during a trim procedure. | R/W | Enum | 0 |
electrical1_digital_units | 4051 | Unit | Unit for Electric input Sensor 1 a) Ohm for resistor thermometer and resistor measurements b) mV for thermocuoples and voltage measurement | R/W | Enum | 0 |
Name | ID | Label | Description | Type | Access | Class |