Name ID Label Description Type Access Class
difference_s1_s2_digital_units 4062 Unit Unit for Difference Measurement (Sensor 1 - Sensor 2) and for all other relevant device variables R/W Enum 0
difference_s1_s2_digital_value 4063 Difference: Sensor 1 - Sensor 2 Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Float 2
damping_value_DiffS1S2 40DC Damping Damping time constant applied to both the Digital Value representation and Analog Value of a respective Analog Output. The units of this variable are always in seconds R/W Float 0
difference_s1_s2_upper_sensor_limit 4064 UpperLimit Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 0
difference_s1_s2_lower_sensor_limit 4065 Lower Limit Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 0
difference_s1_s2_minimum_span 4066 Min Span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 0
snr1snr2qty 40DD Snr1-Snr2 Status Process Data Quality- Indicates the overall process data quality of the device variable value. R Enum 2
difference_s2_s1_digital_units 4068 Unit Unit for Difference Measurement (Sensor 2 - Sensor 1) and for all other relevant device variables R/W Enum 0
difference_s2_s1_digital_value 4069 Difference: Sensor 2 - Sensor 1 Differential Measurement is derived by computing the difference between Sensor 1 and Sensor 2 (Sensor 2 - Sensor 1). Both sensors should be configured. R Float 2
damping_value_DiffS2S1 40DE Damping Damping time constant applied to both the Digital Value representation and Analog Value of a respective Analog Output. The units of this variable are always in seconds R/W Float 0
Name ID Label Description Type Access Class