Name ID Label Description Type Access Class
messart 4000 Тип изм. Type of measurement - Setting of vital input parameters on transmitter. R/W Enum 2048
sensor_typ 4003 Тип сенс Sensor type - Type of currently connected sensor. Depending on the type of selected characteristic line, the measured value is influenced. R/W Enum 8
wire_no 4001 Sensor connection Sensor connection - States the number of wires, via which the sensor is connected to the transmitter. R/W Enum 8
n_sensor 4002 Number of sensors Number of sensors - States the number of sensors which areconnected in series at every input. A multiple number of the built-in characteristic lines can be realised (e.g. 10*Pt100 = Pt1000). R/W Enum 8
sensor_monitor 4004 Sensor monitoring Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. R/W Enum 8
refer_junction 4006 ext. ref. junction External reference junction - The value states the temperature of the external reference junction. The input is always made in °C! R/W Float 8
out_select 4009 Вывод Analog output - The device is only available as signal output 4..20mA. An under- or overrange exceeding this range is however possible. R/W Enum 2048
out_under 400A Underrange value Underrange value - The control range is limited by the underrange value. In case of failure signal, the value is also accepted by means of underranging. R/W Float 8
out_over 400B Overrange value Overrange value - The control range is limited by the overrange value. In case of failure signal, the value is also accepted by means of overranging. R/W Float 8
alter_selector 4005 Failure signalling Failure signalling - The setting indicates the strategy for signalling a failure. R/W Enum 8
alter_value 400C Default value Default value - in case of failure, the analog output is set on the programmed value if the matching error strategy was selected. R/W Float 8
sensor_name 400F Sensor name Sensor name - The function permits the input of a sensor name when using user defined characteristics. R/W PackedAscii 8
order_no 4010 Catalog number Catalog number - The function permits the changing of the catalog number after entering changes on transmitter. R/W PackedAscii 2048
kanal 4013 Signal input Signal input - The setting determines the signal input which must be balanced. W Unsigned 8
sollwert 4014 Уставка Set point - The value states the (e.g. simulated via a reference) input signal. W Float 8
_input_range 402F Input assignment Input assignment - measuring range of the transmitter at the input. W Enum 4096
_type_of_refer_junc 4030 Reference junction Reference junction - The setting determines the type of reference junction during measurements with thermocouples. Always select 'WITHOUT' for measurements witout thermocouples. W Enum 4096
_sensor_monitor 4031 Sensor monitoring Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. W Enum 4096
_failure_control 4035 Failure monitoring Failure monitoring - The setting determines if the analog output should react to certain failure states in the transmitter. R/W Enum 4096
_failure_signal 4036 Signalling Signalling - The setting determines if a failure shall be signalled via the analog output. R/W Enum 4096
_version 4039 Version 1.00 R Enum 4096
digital_units 4017 Единица Единицы измерения переменной полевого устройства - ед.изм., которые должна отображаться с 'Числовым значением', 'Минимальным диапазоном', 'Значение верхнего предела диапазона', 'Значение нижнего предела диапазона', 'Нижний предел сенсора' и 'Верхний предел сенсора' R/W Enum 32
primary_measurement_digital_value 4018 Measured value Measured value - Measured value that changes magnitude with respect to time with no user intervention. R Float 34
primary_measurement_percent_range 403E Measured value Percent of range - Digital value that is proportional to the variable DIGITAL_VALUE with respect to the range defined by the LOWER_RANGE_VALUE and UPPER_RANGE_VALUE. The units of this variable are always in percent. R Float 34
analog_output_transfer_function 403F Функц. передачи Функция передачи - определяет функцию трансформации, которая будет применяться из значения 'Переменная полевого устройства' для 'Аналоговый выход', и значение 'Процент диапазона'. Функция трансформации не влияет на представление цифрового значения. R Enum 32
primary_measurement_upper_range_value 4019 URV Upper range value - Defines the operational endpoint from which the variables ANALOG_VALUE, PERCENT_RANGE are derived. R/W Float 32
primary_measurement_lower_range_value 401A LRV Lower range value - Defines the operational endpoint from which the variables ANALOG_VALUE, PERCENT_RANGE are derived. R/W Float 32
primary_measurement_damping_value 4027 Демпф. Damping value - Damping time applied to both the variables DIGITAL_VALUE and ANALOG_VALUE of output 'X'. The units of this variable are always expressed in seconds. R/W Float 32
sensor_serial_number 4040 Сер ном сенс Серийный номер сенсора - служит уникальным идентификатором сенсора, по которому в первую очередь выводится представление цифрового значения или переменная полевого устройства R/W Unsigned 2048
primary_measurement_upper_sensor_limit 401B USL Upper sensor limit value - Value that defines the absolute upper endpoint (largest magnitude) for the UPPER RANGE VALUE. R Float 8
primary_measurement_lower_sensor_limit 401C LSL Lower sensor limit value - Value that defines the absolute lower endpoint (smallest magnitude) for the LOWER RANGE VALUE. R Float 8
primary_measurement_minimum_span 401D Мин диап Minimum span value - Value that defines the smallest absolute value for the resulting figure derived from the following equation (UPPER RANGE VALUE - LOWER RANGE VALUE). R Float 8
ma_analog_output_value 4041 AO Аналоговый выход - физический выход с возможностью измерения, который меняется в соотвествие с входным воздейстиембез участия пользователя R/W Float 66
ma_analog_output_alarm_select 4042 Alarm type Тип сигнала аналогового выхода - определяет способ отклика аналогового выхода, когда полевое устройство обнаруживает, что аналоговый выход, возможно, не отслеживает связанную переменную полевого устройства. ПРИМЕЧАНИЕ. Представление цифрового значения не может быть определяющим. R Enum 64
electronics_temperature_digital_units 4025 Ед изм. темп-ры CJC Temp. unit of the reference junction temperature - The temperature on the terminal block of the field unit is always stated in °C during measurements with internal or external reference junction. R Enum 34
electronics_temperature_digital_value 4008 Темп CJC Reference junction temperature value - Temperature associated with the internal/external reference junction. At an internal reference junction the temperature of the connection terminals of the transmitter will be measured during measurements. R/W Float 34
sensor1_digital_units 401F Единица Unit - physical unit in which the electrical value of the sensor is expressed. R Enum 34
sensor1_measurement_digital_value 4020 Сенс1 Sensor value - electrical value of the sensor at the input. R Float 34
sensor2_digital_units 4022 Единица Unit - physical unit in which the electrical value of the sensor is expressed. R Enum 34
sensor2_measurement_digital_value 4023 Сенс2 Sensor value - electrical value of the sensor at the auxiliary input. R Float 34
units_code 07E9 R/W Enum 4096
transfer_function_code 07EA R/W Enum 4096
alarm_selection_code 07EB R/W Enum 4096
write_protect_code 07EE R/W Enum 2048
company_identification_code 07EF R/W Enum 128
flag_assignment 07F2 R/W Enum 128
operating_mode_code 07F3 R/W Enum 2048
response_code 0096 Особый код отклика на команду - данные, возвращаемые в ответе полевого устройства, которые указывают результат выполнения команды, отправленной в запросе хоста. Эта информация может относится к данным запроса хоста или к самой команде. R/W Enum 129
comm_status 0098 Сводка ошибок связи - полевое устройство обнаружило следующее состояние ошибки при получении запроса хоста. Поэтому, команда не была получена и запрос хоста не привел к изменению в полевом устройстве. R/W BitEnum 131
device_status 0097 Статус полевого устройства - данные, указывающие на обнаружение полевым устройством условий, связанных с: оборудованием/действительностью переменной/рабочим статусом/внутренним процессом R/W BitEnum 131
Name ID Label Description Type Access Class