Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
messart | 4000 | Tipo de medição | Type of measurement - Setting of vital input parameters on transmitter. | R/W | Enum | 2048 |
sensor_typ | 4003 | Tipo de sensor | Sensor type - Type of currently connected sensor. Depending on the type of selected characteristic line, the measured value is influenced. | R/W | Enum | 8 |
wire_no | 4001 | Sensor connection | Sensor connection - States the number of wires, via which the sensor is connected to the transmitter. | R/W | Enum | 8 |
n_sensor | 4002 | Number of sensors | Number of sensors - States the number of sensors which areconnected in series at every input. A multiple number of the built-in characteristic lines can be realised (e.g. 10*Pt100 = Pt1000). | R/W | Enum | 8 |
sensor_monitor | 4004 | Sensor monitoring | Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. | R/W | Enum | 8 |
refer_junction | 4006 | ext. ref. junction | External reference junction - The value states the temperature of the external reference junction. The input is always made in °C! | R/W | Float | 8 |
out_select | 4009 | Saída | Analog output - The device is only available as signal output 4..20mA. An under- or overrange exceeding this range is however possible. | R/W | Enum | 2048 |
out_under | 400A | Underrange value | Underrange value - The control range is limited by the underrange value. In case of failure signal, the value is also accepted by means of underranging. | R/W | Float | 8 |
out_over | 400B | Overrange value | Overrange value - The control range is limited by the overrange value. In case of failure signal, the value is also accepted by means of overranging. | R/W | Float | 8 |
alter_selector | 4005 | Failure signalling | Failure signalling - The setting indicates the strategy for signalling a failure. | R/W | Enum | 8 |
alter_value | 400C | Default value | Default value - in case of failure, the analog output is set on the programmed value if the matching error strategy was selected. | R/W | Float | 8 |
sensor_name | 400F | Sensor name | Sensor name - The function permits the input of a sensor name when using user defined characteristics. | R/W | PackedAscii | 8 |
order_no | 4010 | Catalog number | Catalog number - The function permits the changing of the catalog number after entering changes on transmitter. | R/W | PackedAscii | 2048 |
kanal | 4013 | Signal input | Signal input - The setting determines the signal input which must be balanced. | W | Unsigned | 8 |
sollwert | 4014 | Setpoint | Set point - The value states the (e.g. simulated via a reference) input signal. | W | Float | 8 |
_input_range | 402F | Input assignment | Input assignment - measuring range of the transmitter at the input. | W | Enum | 4096 |
_type_of_refer_junc | 4030 | Reference junction | Reference junction - The setting determines the type of reference junction during measurements with thermocouples. Always select 'WITHOUT' for measurements witout thermocouples. | W | Enum | 4096 |
_sensor_monitor | 4031 | Sensor monitoring | Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. | W | Enum | 4096 |
_failure_control | 4035 | Failure monitoring | Failure monitoring - The setting determines if the analog output should react to certain failure states in the transmitter. | R/W | Enum | 4096 |
_failure_signal | 4036 | Signalling | Signalling - The setting determines if a failure shall be signalled via the analog output. | R/W | Enum | 4096 |
_version | 4039 | Version 1.00 | R | Enum | 4096 | |
digital_units | 4017 | Unidades | Unidade de variável do dispositivo de campo- Unidade de engenharia para ser apresentada com a representação do valor digital, intervalo mínimo, valor da faixa superior, valor da faixa inferior, limite do sensor inferior, e limite do sensor superior | R/W | Enum | 32 |
primary_measurement_digital_value | 4018 | Measured value | Measured value - Measured value that changes magnitude with respect to time with no user intervention. | R | Float | 34 |
primary_measurement_percent_range | 403E | Measured value | Percent of range - Digital value that is proportional to the variable DIGITAL_VALUE with respect to the range defined by the LOWER_RANGE_VALUE and UPPER_RANGE_VALUE. The units of this variable are always in percent. | R | Float | 34 |
analog_output_transfer_function | 403F | Função Xfer | Transferência de Função-Define a função de transformação que será aplicado a partir de a variável Dispositivo de Campo para a saída analógica, e Faixa de Porcentagem. A transferência Função não afeta a representação Valor Digital. | R | Enum | 32 |
Name | ID | Label | Description | Type | Access | Class |