Name ID Label Description Type Access Class
messart 4000 測定対象 Type of measurement - Setting of vital input parameters on transmitter. R/W Enum 2048
sensor_typ 4003 センサー タイプ Sensor type - Type of currently connected sensor. Depending on the type of selected characteristic line, the measured value is influenced. R/W Enum 8
wire_no 4001 Sensor connection Sensor connection - States the number of wires, via which the sensor is connected to the transmitter. R/W Enum 8
n_sensor 4002 Number of sensors Number of sensors - States the number of sensors which areconnected in series at every input. A multiple number of the built-in characteristic lines can be realised (e.g. 10*Pt100 = Pt1000). R/W Enum 8
sensor_monitor 4004 Sensor monitoring Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. R/W Enum 8
refer_junction 4006 ext. ref. junction External reference junction - The value states the temperature of the external reference junction. The input is always made in °C! R/W Float 8
out_select 4009 出力 Analog output - The device is only available as signal output 4..20mA. An under- or overrange exceeding this range is however possible. R/W Enum 2048
out_under 400A Underrange value Underrange value - The control range is limited by the underrange value. In case of failure signal, the value is also accepted by means of underranging. R/W Float 8
out_over 400B Overrange value Overrange value - The control range is limited by the overrange value. In case of failure signal, the value is also accepted by means of overranging. R/W Float 8
alter_selector 4005 Failure signalling Failure signalling - The setting indicates the strategy for signalling a failure. R/W Enum 8