Name ID Label Description Type Access Class
_sensor_monitor 4035 Sensor monitoring Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. W Enum 4096
_failure_control 4039 Failure monitoring Failure monitoring - The setting determines if the analog output should react to certain failure states in the transmitter. R/W Enum 4096
_failure_signal 403A Signalling Signalling - The setting determines if a failure shall be signalled via the analog output. R/W Enum 4096
CRV_X1 403E Tiepoint_01-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y1 405E Tiepoint_01-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X2 403F Tiepoint_02-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y2 405F Tiepoint_02-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X3 4040 Tiepoint_03-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y3 4060 Tiepoint_03-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X4 4041 Tiepoint_04-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
Name ID Label Description Type Access Class