Name ID Label Description Type Access Class
messart 4000 Meas typ Type of measurement - Setting of vital input parameters on transmitter. R/W Enum 2048
sensor_typ 4003 Snsr typ Sensor type - Type of currently connected sensor. Depending on the type of selected characteristic line, the measured value is influenced. R/W Enum 8
wire_no 4001 Sensor connection Sensor connection - States the number of wires, via which the sensor is connected to the transmitter. R/W Enum 8
n_sensor 4002 Number of sensors Number of sensors - States the number of sensors which are connected in series at every input. A multiple number of the built-in characteristic lines can be realised (e.g. 10*Pt100 = Pt1000). R/W Enum 8
sensor_monitor 4004 Sensor monitoring Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. R/W Enum 8
refer_junction 4007 ext. ref. junction External reference junction - The value states the temperature of the external reference junction. The input is always made in degC! W Float 8
out_select 4009 Output Analog output - The device is only available as signal output 4..20mA. An under- or overrange exceeding this range is however possible. R/W Enum 2048
out_under 400A Underrange value Underrange value - The control range is limited by the underrange value. In case of failure signal, the value is also accepted by means of underranging. R/W Float 8
out_over 400B Overrange value Overrange value - The control range is limited by the overrange value. In case of failure signal, the value is also accepted by means of overranging. R/W Float 8
alter_selector 4005 Failure signalling Failure signalling - The setting indicates the strategy for signalling a failure. R/W Enum 8
alter_value 400C Default value Default value - in case of failure, the analog output is set on the programmed value if the matching error strategy was selected. R/W Float 8
usr_threshold1 400F Threshold 1 Threshold - the measured percent of range will be monitored for an over-/underranging of this threshold.The status can be read by HART only. There is NO influence to the analog output. R/W Float 1024
usr_threshold2 4010 Threshold 2 Threshold - the measured percent of range will be monitored for an over-/underranging of this threshold.The status can be read by HART only. There is NO influence to the analog output. R/W Float 1024
usr_threshold_status 4006 Threshold status Threshold status - the status of the thresholds can be read out. R BitEnum 1027
sensor_name 4013 Curve name Curve name - The function permits the input of a curve name when using the Free style sensortype. R/W PackedAscii 8
kanal 4016 Signal input Signal input - The setting determines the signal input which must be balanced. W Unsigned 8
sollwert 4017 Set pt Set point - The value states the (e.g. simulated via a reference) input signal. W Float 8
_local_messart 4032 Type of measurement Type of measurement - The setting determines, whether single- or multi-channel measurement is active. W Enum 4096
_filter 4033 Mains filter Mains filter - frequency of the local mains to increase the rejection at the input. W Enum 4096
_type_of_refer_junc 4034 Reference junction Reference junction - The setting determines the type of reference junction during measurements with thermocouples. Always select 'WITHOUT' for measurements witout thermocouples. W Enum 4096
_sensor_monitor 4035 Sensor monitoring Sensor monitoring - With this setting the monitoring of the sensors can be limited or released. An internal reference junction is always monitored. W Enum 4096
_failure_control 4039 Failure monitoring Failure monitoring - The setting determines if the analog output should react to certain failure states in the transmitter. R/W Enum 4096
_failure_signal 403A Signalling Signalling - The setting determines if a failure shall be signalled via the analog output. R/W Enum 4096
CRV_X1 403E Tiepoint_01-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y1 405E Tiepoint_01-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X2 403F Tiepoint_02-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y2 405F Tiepoint_02-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X3 4040 Tiepoint_03-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y3 4060 Tiepoint_03-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X4 4041 Tiepoint_04-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y4 4061 Tiepoint_04-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X5 4042 Tiepoint_05-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y5 4062 Tiepoint_05-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X6 4043 Tiepoint_06-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y6 4063 Tiepoint_06-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X7 4044 Tiepoint_07-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y7 4064 Tiepoint_07-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X8 4045 Tiepoint_08-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y8 4065 Tiepoint_08-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X9 4046 Tiepoint_09-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y9 4066 Tiepoint_09-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X10 4047 Tiepoint_10-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y10 4067 Tiepoint_10-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X11 4048 Tiepoint_11-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y11 4068 Tiepoint_11-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X12 4049 Tiepoint_12-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y12 4069 Tiepoint_12-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X13 404A Tiepoint_13-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16
CRV_Y13 406A Tiepoint_13-OUT Tiepoint outputvalue - States the outputvalue of this tiepoint in degC. All tiepoints must be given and the values must be monotone ascent or descent order. R/W Float 16
CRV_X14 404B Tiepoint_14-IN Tiepoint inputvalue - States the inputvalue of this tiepoint in ohms or millivolts. All tiepoints must be given and the values must be monotone ascent order. R/W Float 16