Loading…
Name ID Label Description Type Access Class
alter_value 400C Default value Default value - in case of failure, the analog output is set on the programmed value if the matching error strategy was selected. R/W Float 8
usr_threshold1 400F Threshold 1 Threshold - the measured percent of range will be monitored for an over-/underranging of this threshold.The status can be read by HART only. There is NO influence to the analog output. R/W Float 1024
usr_threshold2 4010 Threshold 2 Threshold - the measured percent of range will be monitored for an over-/underranging of this threshold.The status can be read by HART only. There is NO influence to the analog output. R/W Float 1024
usr_threshold_status 4006 Threshold status Threshold status - the status of the thresholds can be read out. R BitEnum 1027
sensor_name 4013 Curve name Curve name - The function permits the input of a curve name when using the Free style sensortype. R/W PackedAscii 8
kanal 4016 Signal input Signal input - The setting determines the signal input which must be balanced. W Unsigned 8
sollwert 4017 Set pt Set point - The value states the (e.g. simulated via a reference) input signal. W Float 8
_local_messart 4032 Type of measurement Type of measurement - The setting determines, whether single- or multi-channel measurement is active. W Enum 4096
_filter 4033 Mains filter Mains filter - frequency of the local mains to increase the rejection at the input. W Enum 4096
_type_of_refer_junc 4034 Reference junction Reference junction - The setting determines the type of reference junction during measurements with thermocouples. Always select 'WITHOUT' for measurements witout thermocouples. W Enum 4096
Name ID Label Description Type Access Class