Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
Level_Obj_value_0 | 4000 | Level | Height of product in the vessel. | R/W | Float | 2 |
Level_Obj_unit | 4001 | Level Unit | Engineering Units for the distance measurements. | R/W | Enum | 0 |
levelPDQ | 4002 | Level Data Quality | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 2 |
levelLS | 4003 | Level Limit Status | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 2 |
Level_Status | 4004 | Level Status | Device Family Status- Indicates additional status information on a device variable for a specific device family. | R | BitEnum | 2 |
Level_Classification | 4005 | Level Classification | Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. | R | Enum | 0 |
LeveldeviceVariableFamilyCodes_Level | 4006 | Level Device Family | Device Family- Indicates the family (i.e, pressure, temperature, flow, etc.) that the device variable belongs. | R | Enum | 0 |
Level_UpperRange_Obj_value_0 | 4007 | Lvl USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 0 |
Level_LowerRange_Obj_value_0 | 4008 | Lvl LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 0 |
Level_MinimumSpan_Obj_value_0 | 4009 | Level Minimum Span | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 0 |
Level_DampingTime | 400A | Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 0 |
LevelSim_Enable | 400B | Simulation | Level value simulation status. | R/W | Enum | 0 |
LevelmainTaskDelayTimeMax | 400C | Level Update Period | R | Time | 0 | |
LeveltransducerSerialNumber | 400D | Sensor s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 0 |
linearized_levelPDQ | 400F | LIN 0 Data Quality | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 2 |
linearized_levelLS | 4010 | LIN 0 Limit Status | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 2 |
LinLevel_Status | 4011 | LIN 0 Level Status | Device Family Status- Indicates additional status information on a device variable for a specific device family. | R | BitEnum | 0 |
Lin_Classification | 4012 | Output Type | Linearization output type. | R/W | Enum | 0 |
LindeviceVariableFamilyCodes_Level | 4015 | Level Device Family | Device Family- Indicates the family (i.e, pressure, temperature, flow, etc.) that the device variable belongs. | R | Enum | 0 |
LIN_Level_UpperRange | 4016 | LIN 0 Upper Sensor Limit | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 0 |
LIN_Level_LowerRange | 4017 | LIN 0 Lower Sensor Limit | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 0 |
LIN_Level_MinimumSpan | 4018 | LIN 0 Minimum Span | Linearized Level Minimum Span | R | Float | 0 |
LinmainTaskDelayTimeMax | 4019 | LIN 0 Update Period | R | Time | 0 | |
LintransducerSerialNumber | 401A | Sensor Serial Number | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 0 |
LinLevel_FlowObj_value_0 | 401B | Flow | Linearized flow value | R/W | Float | 2 |
LinLevel_FlowObj_unit | 401C | Flow Unit | R/W | Enum | 0 | |
Lin_Volume_Flow_Classification | 401D | Flow Classification | Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. | R/W | Enum | 0 |
LinLevel_FlowDampingTime | 401E | LIN Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 0 |
LinLevel_FlowSim_Enable | 401F | Simulation | Linearized Level value simulation status. | R/W | Enum | 0 |
LinLevel_VolumeObj_value_0 | 4021 | Volume | Linearized volume value | R/W | Float | 2 |
LinLevel_VolumeObj_unit | 4022 | Volume Unit | R/W | Enum | 0 | |
Lin_Volume_Classification | 4023 | Volume Classification | Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. | R/W | Enum | 0 |
LinLevel_VolumeDampingTime | 4024 | LIN Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 0 |
LinLevel_VolumeSim_Enable | 4025 | Simulation | Linearized Level value simulation status. | R/W | Enum | 0 |
Ullage_Obj_value_0 | 4027 | Ullage | Ullage Value | R/W | Float | 2 |
ullagePDQ | 4028 | Ullage Data Quality | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 2 |
ullageLS | 4029 | Ullage Limit Status | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 2 |
Ullage_Status | 402A | Ullage Status | Device Family Status- Indicates additional status information on a device variable for a specific device family. | R | BitEnum | 2 |
UllageLevel_Classification | 402B | Ullage Classification | Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. | R | Enum | 0 |
UllagedeviceVariableFamilyCodes_Level | 402C | Level Device Family | Device Family- Indicates the family (i.e, pressure, temperature, flow, etc.) that the device variable belongs. | R | Enum | 0 |
Ullage_UpperRange_Obj_value_0 | 402D | Ullage Upper Sensor Limit | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 0 |
Ullage_LowerRange_Obj_value_0 | 402E | Ullage Lower Sensor Limit | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 0 |
Ullage_MinimumSpan | 402F | Ullage Minimum Span | Ullage Minimum Span | R | Float | 0 |
UllageLevel_DampingTime | 4030 | Ullage Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 0 |
UllageSim_Enable | 4031 | Simulation | Ullage value simulation status. | R/W | Enum | 0 |
UllagemainTaskDelayTimeMax | 4032 | Ullage Update Period | R | Time | 0 | |
UllagetransducerSerialNumber | 4033 | Sensor Serial Number | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 0 |
Interface_Obj_value_0 | 4035 | Interface | Interface is the height at which a surface forms a common boundary between two immiscible liquids. | R/W | Float | 2 |
interfacePDQ | 4036 | Interface Data Quality | Process Data Quality- Indicates the overall process data quality of the device variable value. | R | Enum | 2 |
interfaceLS | 4037 | Interface Limit Status | Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). | R | Enum | 2 |
Name | ID | Label | Description | Type | Access | Class |