名称 ID 标签 描述 类型 访问 分类
temperaturePDQ 4054 Temperature Data Quality 枚举 2
temperatureLS 4055 Temperature Limit Status 枚举 2
T_Status 4056 Temperature Status 设备类别状态——表示特定设备类别的设备变量的额外状态信息。 位枚举 0
T_Classification 4057 Temperature Classification 枚举 0
deviceVariableFamilyCodes_Temp 4058 设备族 枚举 0
T_UpperRange_Obj_value_0 4059 Temperature USL 传感器上限值——定义上限值的最大可用数值。 浮点 0
T_LowerRange_Obj_value_0 405A Temperature LSL 传感器下限值——定义上限值的最小可用数值。 浮点 0
T_MinimumSpan_Obj_value_0 405B Minimum Span 最小范围值——定义上限值和下限值之间允许的最小差。 浮点 0
T_DampingTime 405C Damping Damping Value- Damping time constant applied to temperature value. The units of this variable are always in seconds. 读/写 浮点 0
TSim_Enable 405D Simulation Temperature value simulation status. 读/写 枚举 0
TmainTaskDelayTimeMax 405E Temperature Update Period 时间 0
T_transducerSerialNumber 405F Temperature Sensor Serial Number 传感器序列号——识别数值表示或现场设备变量来源的传感器。 无符号 0
swWriteProtection 4113 SW Write Protection Indicates whether variables can be written to the Field Device, or whether commands that cause actions to be performed in the Field Device, can or cannot occur. 读/写 枚举 0
mountOrientation 4118 Mounting Orientation Device may be either Top or Bottom Mounted. 读/写 枚举 0
serviceCodeLogOut 4149 Service Code Logout Service Code Logout 无符号 0
T_Offset_Obj_Value_0 40C4 Offset Offsets the temperature value read from the RTD at the bottom of the probe. 读/写 浮点 0
HartClearDiagnosticsHistory 414C 无符号 0
totalWorkingTimeHour 414E Total Run Time Total run time in days since last device reset. 无符号 2
cpuLoad 414F CPU Load Percent of CPU load. 浮点 2
alarm_delay 411A Alarm Delay The output will go to alarm state only if there is a loss of signal that lasts at least the duration of the alarm delay. 读/写 浮点 0
pulseWidth 411B Pulse Width Amount of energy used for the level measurement. 读/写 无符号 0
levelDeviceType 4014 Device Configuration Options include 1 or 2 Levels and with or without Temperature. 读/写 枚举 0
blanking 406E Blanking Distance Blanking is a measured area which the LMT will be set to ignore including the nozzle distance. It may be necessary to extend the Blanking further past the nozzle to ignore reflections from the top portion of the probe. Blanking is set in terms of units. To adjust the Blanking, enter the distance from the Reference Measurement to be ignored. Do not blank into your measuring range. Signal will be lost. 读/写 浮点 0
readOnlySwitchStatus 4114 Status Hardware switch that allows remote access. 枚举 0
cbSoftwareRevisionChars 4154 Software Revision Electronics software revision. ASCII 0
名称 ID 标签 描述 类型 访问 分类