Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
HartPollingAddress | 402A | Poll.addr. | An adress 0-15 can be selected for instruments with the HART-Protocol. If the adress 0 is entered, then the current output varies as the flowrate in the range of 4-20 mA. If additional instruments are connected to the bus and a adress 1-15 is entered, the converter operates in Multidrop-Mode. The current output is fixed at constant 4mA. The output values are then only can only be read using the HART-Communication. | R/W | Unsigned | 2048 |
ucAnzeigeModus | 4043 | Display mode | Selection 1 large and 1 small line or 4 small lines. | R/W | Enum | 2048 |
ucAnzeigeKontrast | 409C | Contrast | Setting the display contrast, STEP = darker; DATA = lighter. | R/W | Unsigned | 2048 |
ucKommunikation | 409E | Communication | Turn HART -Communication on and off. | R/W | Enum | 2048 |
ucTreiber | 40A0 | Driver | Selects the mode of the driver | R/W | Enum | 2048 |
ucBestellVariante | 40A2 | Communication | The calibrating mode 0 or 255 can be select. With mode 0 the primarys SE2_/SE4_ are calibrated together with converter. The meter size and adjusted value are primary accompanying. At mode 255 the converter can delivered to connect with old primary model, Cs = 100% and Cz = 0% be printed on the FRAM. The customer can select meter size and excitation frequency with ENTER. The EASY SETUP for a old primary must be followed for operation. | R/W | Unsigned | 2048 |
ucNetzfrequenz | 40A4 | Line frequency | Selection of the line frequency of the flowmeter primary was calibrated. Selection 50/60 Hz only available for Older Models. | R/W | Enum | 2048 |
ucStartUpKommuService | 40A6 | Startup Commu. | With a TTL-Signal the communication type HART or ASCII can be selected of the service plug for the connection. | R/W | Enum | 2048 |
ucTestImpulsausgangEin | 40A8 | Startup Commu. | Function test for the pulse output. | R/W | Enum | 2048 |
ucIoutArt | 40AA | Current output | Selection of the current output range. For HART-Protocol always 4-20 mA. | R/W | Enum | 2048 |
Name | ID | Label | Description | Type | Access | Class |