名称 ID 标签 描述 类型 访问 分类
code_number 4087 Code number code number 读/写 无符号 2048
instr_number 400A 设备ID 现场设备ID——与厂商ID和设备类型结合用于识别现场设备。因此,该变量不能由主机用户修改。 无符号 2048
calibration_mode 4043 Calibration mode calibration mode 读/写 无符号 2048
unsigned_int_variable_code 408C 动态变量阵列索引——识别相对于时间动态的现场设备变量,无需用户输入。 读/写 索引 4096
range_2 4000 Range 2 Only valid if operating mode is set to 2 FLOW RANGE. Range 2 from 0.05*Range DN to upper range value. 读/写 浮点 2048
pulse_factor 4001 Pulse factor pulse factor from 0.001 to 1000 per selected unit. Max. count frequency is 5 kHz. Depends on the the selected pulse width and will be automaticly corrected. 读/写 浮点 2048
pulse_width 401F Pulse width pulse width from 0.1 to 2000 ms. Depends on the the selected pulse factor and will be automaticly corrected. 读/写 浮点 2048
low_flow_cut_off 400E Low flow cutoff Low flow cutoff from 0 to 10% of the selected flow upper range value. 读/写 浮点 2048
density 4021 Density Density in the range from 0.01 to 5 g/cm3 for mass flow. 读/写 浮点 2048
system_zero_adjust 400F System zero system zero from -50 to 50 Hz 读/写 浮点 2048