Name ID Label Description Type Access Class
code_number 4087 Code number code number R/W Unsigned 2048
instr_number 400A Dev id Field Device Identification- Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified by the Host user. R Unsigned 2048
calibration_mode 4043 Calibration mode calibration mode R/W Unsigned 2048
unsigned_int_variable_code 408C Index into Dynamic Variables Array- An index that identifies a Field Device Variable that is dynamic with respect to time, with no user input R/W Index 4096
range_2 4000 Range 2 Only valid if operating mode is set to 2 FLOW RANGE. Range 2 from 0.05*Range DN to upper range value. R/W Float 2048
pulse_factor 4001 Pulse factor pulse factor from 0.001 to 1000 per selected unit. Max. count frequency is 5 kHz. Depends on the the selected pulse width and will be automaticly corrected. R/W Float 2048
pulse_width 401F Pulse width pulse width from 0.1 to 2000 ms. Depends on the the selected pulse factor and will be automaticly corrected. R/W Float 2048
low_flow_cut_off 400E Low flow cutoff Low flow cutoff from 0 to 10% of the selected flow upper range value. R/W Float 2048
density 4021 Density Density in the range from 0.01 to 5 g/cm3 for mass flow. R/W Float 2048
system_zero_adjust 400F System zero system zero from -50 to 50 Hz R/W Float 2048
Name ID Label Description Type Access Class