Name ID Label Description Type Access Class
k4 4065 k4 k-factor k4 for k-factor linearisation. Please refer to calibration protocol! R/W Float 2048
k5 4067 k5 k-factor k5 for k-factor linearisation. Please refer to calibration protocol! R/W Float 2048
float_variable_code 40F0 Index into Dynamic Variables Array- An index that identifies a Field Device Variable that is dynamic with respect to time, with no user input R/W Index 4096
units_code 07E9 R/W Enum 4096
response_code 0096 Command Specific Response Code- Data that is returned in the Field Device response, that indicates the relative success of the Command sent in the Host request. This information may relate to the Data of the Host request or to the command itself. R/W Enum 4096
comm_status 0098 Communications Error Summary- The Field Device has detected the following error condition while attempting to receive the Host request. Therefore the Command was not accepted, and the Host request caused no change to occur in the Field Device. R/W BitEnum 131
device_status 0097 Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process R/W BitEnum 131
manufacturer_id 0099 Produttore Codice identificazione produttore - Si riferisce ad un produttore specifico, solitamente il nome di una società, che è responsabile della produzione del dispositivo di campo. R Enum 128
device_type 009A Model Model- References the type of Field Device, usually an advertised model number, that is unique to a single manufacturer R Enum 128
request_preambles 009B Num req preams Number of Request Preambles- Number of Preambles required from the Host request by the Field Device R Unsigned 128
universal_revision 009C Universal rev Universal Revision- Revision of the Universal Device Description, that the Field Device conforms to R Unsigned 128
transmitter_revision 009D Fld dev rev Field Device Revision- Revision of the Field Device Specific Device Description, that the Field Device conforms to R Unsigned 128
software_revision 009E Software rev Field Device Software Revision- This revision corresponds to the software or firmware, that is embedded in the Field Device R Unsigned 2048
hardware_revision 009F Hardware rev Versione hardware - Versione che corrisponde all’hardware dell’elettronica del dispositivo di campo. R Unsigned 2048
physical_signaling_code 00AB Physicl signl code Physical Signaling Code- The Physical Signaling Code describes the type of Physical Layer that has been implemented in the hardware that is responsible for the HART Communication port R Enum 2048
device_flags 00A0 Dev flags Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer R BitEnum 128
device_id 00A1 Dev id Field Device Identification- Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified by the Host user. R Unsigned 128
polling_address 00A2 Poll addr Polling Address- Address used by the Host to identify a Field Device, and changeable by the User to control: the Multidrop Mode for Analog Output 1), and the Analog Output Fixed Mode of Analog Output 1) W Unsigned 128
tag 00A3 Tag Tag - Testo associato all’installazione del dispositivo di campo. Questo testo può essere utilizzato dall’utente in qualsiasi modo. Un uso consigliato è come etichetta univoca per un impianto che si correla all’etichetta di un dispositivo di campo: un disegno dell’impianto o su un sistema di controllo. Questa variabile viene utilizzata anche come tipo di handle di indirizzo a livello di collegamento dati. R/W PackedAscii 2048
message 00A4 Messaggio Messaggio - Testo associato al dispositivo di campo. Questo testo può essere utilizzato dall’utente in qualsiasi modo. Non esiste un uso raccomandato. R/W PackedAscii 2048
descriptor 00A5 Descrittore Descriptor- Text that is associated with the Field Device. This text can be used by the user in any way. There is no specific recommended use. R/W PackedAscii 2048
date 00A6 Data Data - Data del calendario gregoriano che viene memorizzata nel dispositivo di campo. Questa data può essere utilizzata dall’utente in qualsiasi modo. Non esiste un uso specifico raccomandato. R/W HartDate 2048
write_protect 00A7 Write protect Write Protect Mode- Indicates whether variables can be written to the Field Device, or whether commands that cause actions, to be performed in the Field Device, can or cannot occur. Depending on the Field Device, this is a mode that is controllable by the user, either via the Field Device hardware or the HART Protocol. R Enum 2048
private_label_distributor 00A8 Distributore Private Label Distributor- References the company that is responsible for the distribution of this Field Device to customers R Enum 2048
final_assembly_number 00A9 Final asmbly num Numero di gruppo finale - Numero che viene utilizzato a scopo di identificazione ed è associato al dispositivo di campo complessivo. R/W Unsigned 2048
transmitter_variable_code_1 0FA0 Index into Dynamic Variables Array- Is the first an array of addresses, whose value is identified by the Field Device Variable Code R/W Index 4096
transmitter_variable_code_2 0FA2 Index into Dynamic Variables Array- Is the second of an array of addresses, whose value identified by the Field Device Variable Code R/W Index 4096
transmitter_variable_code_3 0FA3 Index into Dynamic Variables Array- Is the third of an array of addresses, whose value identified by the Field Device Variable Code R/W Index 4096
transmitter_variable_code_4 0FA4 Index into Dynamic Variables Array- Is the fourth of an array of addresses, whose value identified by the Field Device Variable Code R/W Index 4096
primary_variable_code 0FD0 PV is Primary Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Primary Variable dynamic variable R/W Index 128
secondary_variable_code 0FD1 SV is Secondary Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Secondary Variable dynamic variable R/W Index 128
tertiary_variable_code 0FD2 TV is Tertiary Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Tertiary Variable dynamic variable R/W Index 128
fourth_variable_code 0FD3 4V is Fourth Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Fourth Variable dynamic variable R/W Index 128
burst_command_number 0FFD Burst option Opzione burst - Consente di selezionare le variabili che verranno sottoposte a trasferimento burst se è abilitata la modalità burst. W Enum 128
burst_mode_select 0FFF Burst mode Burst Mode Select- Selects the mode for the Burst Mode functionality. If Burst is enabled the Field Device will generate HART messages on the Link without individual requests from the Host. W Enum 128
eeprom_select 0FAB Selezione EEPROM Selezione EEPROM - Consente di controllare i dati in: memoria di sola lettura EEPROM/memoria di sola lettura. R/W Enum 4096
flow_alarm_select 1F83 AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R Enum 64
flow_analog_value 1F7D AO1 Valore uscita analogica - Valore che traccia la rappresentazione del valore digitale, sotto le modalità operative normali R/W Float 66
flow_damping_value 1F87 PV Damp Valore di smorzamento - Costante di tempo di smorzamento applicata sia alla rappresentazione del valore digitale che al valore analogico della rispettiva uscita analogica. Le unità di questa variabile sono sempre in secondi. R/W Float 32
flow_lower_range_value 1F86 PV LRV Valore di campo inferiore - Definisce il punto finale operativo da cui si ricava il valore analogico e il punto 0% del campo percentuale. Inoltre, il valore di campo inferiore definisce un punto finale operativo da cui derivano gli allarmi associati al valore analogico e gli allarmi associati alla rappresentazione del valore digitale. R/W Float 32
flow_lower_sensor_limit 1F80 PV LSL Valore limite sensore inferiore - Definisce il valore minimo utilizzabile per il valore di campo inferiore. R/W Float 8
flow_minimum_span 1F81 PV Min span Valore intervallo minimo - Definisce la differenza più piccola consentita tra il valore di campo superiore e il valore di campo inferiore. R/W Float 32
flow_percent_range 1F7E PV % rnge Percentuale di campo - Variabile che traccia la rappresentazione del valore digitale rispetto al campo definito dal valore di campo inferiore e dal valore di campo superiore, per le modalità operative normali. Le unità di questa variabile sono sempre in percentuale. R/W Float 34
flow_sensor_serial_number 1F82 PV Snsr s/n Numero di serie sensore - Identifica in modo univoco il sensore da cui deriva principalmente la rappresentazione del valore digitale o la variabile dispositivo di campo. R/W Unsigned 2048
flow_upper_range_value 1F85 PV URV Valore di campo superiore - Definisce il punto finale operativo da cui deriva il valore analogico e il punto 100% del campo percentuale. Inoltre, il valore di campo superiore definisce un punto finale operativo da cui derivano gli allarmi associati al valore analogico e gli allarmi associati alla rappresentazione del valore digitale. R/W Float 32
flow_upper_sensor_limit 1F7F PV USL Valore limite sensore superiore - Definisce il valore massimo utilizzabile per il valore di campo superiore. R/W Float 8
transfer_function 1F84 Xfer fnctn Funzione trasferimento - Definisce la funzione di trasformazione che sarà applicata dalla variabile del dispositivo di campo all’uscita analogica e al campo percentuale. La funzione di trasferimento non influisce sulla rappresentazione del valore digitale. R Enum 64