Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
secondary_variable_code | 0FD1 | SV is | Secondary Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Secondary Variable dynamic variable | R/W | Index | 128 |
tertiary_variable_code | 0FD2 | TV is | Tertiary Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Tertiary Variable dynamic variable | R/W | Index | 128 |
fourth_variable_code | 0FD3 | 4V is | Fourth Index into Dynamic Variables Array- An index location, that indicates which Field Device dynamic variable has been mapped into the Fourth Variable dynamic variable | R/W | Index | 128 |
burst_command_number | 0FFD | Burst option | Burst Option- Selects the variable(s) that will be Bursted if Burst Mode is enabled. | W | Enum | 128 |
burst_mode_select | 0FFF | Burst mode | Burst Mode Select- Selects the mode for the Burst Mode functionality. If Burst is enabled the Field Device will generate HART messages on the Link without individual requests from the Host. | W | Enum | 128 |
eeprom_select | 0FAB | EEPROM select | Electrically Erasable Read Only Memory Selection- Controls the data in: EEPROM Read Only Memory / Read Only Memory. | R/W | Enum | 4096 |
flow_alarm_select | 1F83 | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
flow_analog_value | 1F7D | AO1 | Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes | R/W | Float | 66 |
flow_damping_value | 1F87 | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
flow_lower_range_value | 1F86 | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
Name | ID | Label | Description | Type | Access | Class |