Loading…

Variable Name: measurement_type

Variable ID: 0x4009

Variable Label: Meas typ

Variable Help: Measurement type - Indicates the type of measurement: single/differential or average, internal/external or const CJC, external CJC sensor Pt100 or Ni100, 2/3 or 4 wire.

Variable Handling: R/W

Variable Class: Device

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x000D RTD/Ohm sgl 2-wire
0x000E RTD/Ohm sgl 3-wire
0x000F RTD/Ohm sgl 4-wire
0x0004 RTD/Ohm diff 2-wire
0x0010 RTD/Ohm avg 2-wire
0x0005 TC/V sgl int CJC
0x0006 TC/V sgl ext CJC Pt
0x0007 TC/V sgl ext CJC Ni
0x0008 TC/V sgl const. CJC
0x0000 TC/V diff int CJC
0x0001 TC/V diff ext CJC Pt
0x0002 TC/V diff ext CJC Ni
0x0003 TC/V diff const. CJC
0x0009 TC/V avg int CJC
0x000A TC/V avg ext CJC Pt
0x000B TC/V avg ext CJC Ni
0x000C TC/V avg const. CJC

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
140 4037 read_config_data

Variable Write Command List

Command Number Command ID Command Name
141 4038 Write_config_data