Loading…

Variable Name: static_pressure_units

Variable ID: 0x4061

Variable Label: SP Unit

Variable Help: Static Pressure Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit for the Static Pressure.

Variable Handling: R/W

Variable Class: Correction

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0007 bar
0x0008 mbar
0x000B Pa
0x000C kPa
0x000E atm
0x00ED MPa
0x00AE hPa

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
148 4077 read_pres_n_sp_hl_alarm_configuration
169 40B1 read_sp_trim_points_and_devs
135 4171 read_static_press_configuration
173 4175 read_static_press_range_limits
3 00B1 read_dynamic_variables_and_pv_current

Variable Write Command List

Command Number Command ID Command Name
137 4064 write_static_press_unit