Variable Name: pressure1_hysteresis
Variable ID: 0x4058
Variable Label: Pressure 1 Hyst:
Variable Help: Pressure 1 Hysteresis Value, used to generate pressure Alerts from Full-Stroke Signature Run-Time data and PST signatures if the Maintenance Signature supply pressure 1 or break pressure 1 deviates from the Baseline pressure 1 by this value. Note, this hysteresis should have a lower threshold than the PST break pressure hysteresis used for PST break pressure failure alerts since this dictates when a valve/actuator is deviating from it's Baseline performance (trending toward possible future failure). The allowed range is 0.0-20.0%.
Variable Handling: R/W
Variable Class: Dynamic
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.1f
Variable Edit Format: |en|4.1f
Variable Unit:
Variable Max: 20
Variable Min: 0
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
132 | 426C | read_hysteresis_configuration |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
133 | 426D | write_hysteresis_configuration |