Variable Name: dynamic_baseline
Variable ID: 0x405B
Variable Label: Dyn. Baseline Cycle:
Variable Help: Allows setting a process valve cycle count for manual operation of the valve where once this count is reached, a Baseline Signature is collected as part of in process operation. This allows a break-in period for new valves where a Baseline Signature can be collected in process without direct intervention by the device on behalf of the user. A value of 0 disables and the minimum is 2 cycles and up to a maximum of 255. The cycle before the baseline is collected is when the device measures the speed of the valve which is why a minimum of 2 cycles is required.
Variable Handling: R/W
Variable Class: Dynamic
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
130 | 426A | read_basic_configuration |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
131 | 426B | write_basic_configuration |