Loading…

Variable Name: dynamic_baseline

Variable ID: 0x405B

Variable Label: Dyn. Baseline Cycle:

Variable Help: Allows setting a process valve cycle count for manual operation of the valve where once this count is reached, a Baseline Signature is collected as part of in process operation. This allows a break-in period for new valves where a Baseline Signature can be collected in process without direct intervention by the device on behalf of the user. A value of 0 disables and the minimum is 2 cycles and up to a maximum of 255. The cycle before the baseline is collected is when the device measures the speed of the valve which is why a minimum of 2 cycles is required.

Variable Handling: R/W

Variable Class: Dynamic

Variable Size: 1

Variable DataType: Unsigned

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
130 426A read_basic_configuration

Variable Write Command List

Command Number Command ID Command Name
131 426B write_basic_configuration