Variable Name: close_pstn_hysteresis
Variable ID: 0x4057
Variable Label: Close Pstn Hyst:
Variable Help: Close Position Hysteresis Value, this value serves several puposes. It is used to determine valid close start/end position threshold for signature and Run-Time capture, end point for valve speed determination in close direction, and finally for PST break position determination in Fail-Open valves. For example in PST, a 2% value means valve must move at least 2% from start position to detect break. In general, the default value should be suitable but may be modified to compensate for any play between the valve linkage and position sensor. Currently one warning alert can be generated based upon this, Close Position Alert. The allowed range is 0.0-20.0%.
Variable Handling: R/W
Variable Class: Dynamic
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.1f
Variable Edit Format: |en|4.1f
Variable Unit:
Variable Max: 20
Variable Min: 0
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
132 | 426C | read_hysteresis_configuration |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
133 | 426D | write_hysteresis_configuration |