Loading…
Loading…
Variable Name: PST_break_time_hysteresis
Variable ID: 0x405A
Variable Label: PST Brk Time Hyst:
Variable Help: Alert criteria - PST Break Time Hysteresis Value (0-50%) is used to set an allowable limit +- for the Maintenance PST Break Time to deviate from the Baseline PST Break Time at which point a PST Fast/Slow Break Time Alert is generated. The allowed range is 0.0-50.0 seconds.
Variable Handling: R/W
Variable Class: Dynamic | Device
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.1f
Variable Edit Format: |en|4.1f
Variable Unit:
Variable Max: 50
Variable Min: 0
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
134 | 426E | read_PST_configuration |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
135 | 426F | write_PST_configuration |