Variable Name: device_status
Variable ID: 0x0097
Variable Label: Device status
Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process
Variable Handling: R
Variable Class: Dynamic | Diagnostic | HART
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Process applied to the primary variable is outside the operating limits of the field device |
0x0002 | Process applied to the non-primary variable is outside the operating limits of the field device |
0x0004 | PV Analog Channel Saturated |
0x0008 | PV Analog Channel Fixed |
0x0010 | Field device has more status available |
0x0020 | A reset or self test of the field device has occurred, or power has been removed and reapplied |
0x0040 | A modification has been made to the configuration of the field device |
0x0080 | Field device has malfunctioned due to a hardware error or failure |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
169 | 4019 | read_URV_span_adjustment |
137 | 401B | read_zero_elevation |
148 | 401F | read_heavier_density |
183 | 4021 | read_gas_lighter_density |
171 | 4025 | set_URV_span |
163 | 4026 | read_ADC |
174 | 4027 | set_LRV_span |
0 | 00AE | read_unique_identifier |
1 | 00AF | read_pv |
2 | 00B0 | read_pv_current_and_percent_range |
3 | 00B1 | read_dynamic_variables_and_pv_current |
7 | 00DB | read_loop_configuration |
12 | 00B4 | read_message |
13 | 00B5 | read_tag_descriptor_date |
14 | 00B6 | read_pv_sensor_info |
15 | 00B7 | read_pv_output_info |
16 | 00B8 | read_final_assembly_number |
Variable Write Command List
None