Loading…

Variable Name: valve_unallowed_movement_latch_time

Variable ID: 0x4021

Variable Label: Unintended Valve Movement Latch Time

Variable Help: Latch time for setpoint/position deviation in unintended valve movement detection. Latch time is activated when valve position deviates more than 1%. Valve moves, but setpoint remains stable. You must configure latch values to ensure that fast measurement peaks are not causing false alarms.

Variable Handling: R/W

Variable Class: Diagnostic | Device

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|5.1f

Variable Edit Format: |en|5.1f

Variable Unit:

Variable Max: 60

Variable Min: 0

Variable Read Command List

Command Number Command ID Command Name
163 4697 read_online_diagnostics_limits_part1

Variable Write Command List

Command Number Command ID Command Name
131 4589 write_float_parameter