Variable Name: flow_switch_hysteresis
Variable ID: 0x4030
Variable Label: Hysteresis (0.1-10.0)
Variable Help: If the hysteresis is set to 5%, no change of the Discrete Output state occurs when the flow rate is within +-5% of the setpoint. If the setpoint is 100 lb/min and the first reading is below 95 lb/min, the flow switch turns On and will stay On until the flow rate rises above 105 lb/min. At this point it turns Off, and will stay off until the flow rate drops below 95 lb/min.
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|4.2f
Variable Edit Format: |en|4.4f
Variable Unit:
Variable Max:
Variable Min:
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
138 | 402C | read_flow_switch_setpoint |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
139 | 4031 | write_flow_switch_setpoint |