Variable Name: flow_switch_hysteresis

Variable ID: 0x4030

Variable Label: Hysteresis (0.1-10.0)

Variable Help: If the hysteresis is set to 5%, no change of the Discrete Output state occurs when the flow rate is within +-5% of the setpoint. If the setpoint is 100 lb/min and the first reading is below 95 lb/min, the flow switch turns On and will stay On until the flow rate rises above 105 lb/min. At this point it turns Off, and will stay off until the flow rate drops below 95 lb/min.

Variable Handling: R/W

Variable Class: Correction

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|4.2f

Variable Edit Format: |en|4.4f

Variable Unit:

Variable Max:

Variable Min:

Variable Read Command List

Command Number Command ID Command Name
138 402C read_flow_switch_setpoint

Variable Write Command List

Command Number Command ID Command Name
139 4031 write_flow_switch_setpoint