Variable Name: Word_422
Variable ID: 0x43EC
Variable Label: Status Word 422
Variable Help: Reads Modbus register no. 422
Variable Handling: R
Variable Class: Dynamic | Correction
Variable Size: 2
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | API.VCF: Temperature Outside Standard Range |
0x0002 | API.VCF:Line Density Outside Standard Range |
0x0004 | Line RTD Temperature Out-Of-Range |
0x0008 | Meter RTD Temperature Out-Of-Range |
0x0010 | Flow Direction (0=Forward/Zero, 1=Reverse) |
0x0020 | Factory Configuration Data Is Invalid |
0x0040 | Enhanced Density: Unable to fit curve data |
0x0080 | Last Measured Value Override Active |
0x0100 | Enhanced Density Extrapolation Alarm |
0x0200 | Cal Factors Unentered (Flocal Mandatory) |
0x0400 | 1000/2000/3000 EEPROM Checksum Error |
0x0800 | 1000/2000/3000 RAM Test Error |
0x1000 | Unrecognized/Unentered Sensor Type (K1 Manditory) |
0x2000 | Core configuration database corrupt |
0x4000 | Core powerdown totals corrupt |
0x8000 | Core program corrupt |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
215 | 41EA | read_additional_diags |
Variable Write Command List
None