Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label:

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
128 415A read_static_data_material_and_sensor
130 415C read_static_data_special_mass_units
131 415D read_static_data_setup_parameters
132 415E read_flocal_number
132 415E read_flocal_number
138 4163 read_pv_low_flow_cutoff
140 4165 read_static_data_special_volume_units
153 4169 read_density_cal_number
167 416D read_zeroing_time
170 4170 read_max_pulse_width
173 4172 read_control_output
175 4173 read_temperature_cal_factor
179 4175 read_zeroing_info
181 4176 read_fault_output
193 417C read_viscosity_info
195 417E read_specified_cutoff
197 4180 read_present_freq
198 4181 read_density_parameters
200 4183 read_alarm_parameters
203 4186 read_alarm_variable_assignment
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
16 00B8 read_final_assembly_number
33 0FA5 read_transmitter_variables
48 0FCE read_additional_transmitter_status
50 0FD4 read_transmitter_variable_assignments
54 0FDA read_transmitter_variable_information
60 0FE5 read_analog_output_and_percent_of_range
61 0FE7 read_dynamic_variables_and_pv_analog_output
63 0FED read_analog_output_information
70 0FF5 read_analog_output_endpoint_values
110 1001 read_all_dynamic_variables

Variable Write Command List

None