Variable Name: SZHeight
Variable ID: 0x487B
Variable Label: Safety Zone Height
Variable Help: Allows for configuration of an area below the Top Blocking Distance called Safety Zone. Since performance within the Top Blocking Distance is indeterminate, these parameters allow the user to program an area below the Top Blocking Distance where an alarm can be set. Enable fault to ensure safe, reliable high-level readings in critical applications like overfill. (Recommendation is to use Latch 3.6 or Latch 22, so unit will remain in alarm until it is manually cleared with the SZ Alarm Reset.)
Variable Handling: R/W
Variable Class:
Variable Size: 4
Variable DataType: Float
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max:
Variable Min:
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
209 | 4A1B | read_SZHeight |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
210 | 4A1C | set_SZHeight |