Loading…

Variable Name: SZFault

Variable ID: 0x487A

Variable Label: Safety Zone Alarm

Variable Help: Defines how the Analog Output will respond when the transmitter detects a level within the Safety Zone. Enable fault to ensure safe, reliable high-level readings in critical applications. (Recommendation is to use Latch 3.6 or Latch 22, so the unit will remain in alarm until it is manually cleared with the SZ Alarm Reset.)

Variable Handling: R/W

Variable Class:

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 None
0x0001 3.6 mA
0x0002 22 mA
0x0003 Latch 3.6 mA
0x0004 Latch 22 mA

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
207 4A19 read_SZFault

Variable Write Command List

Command Number Command ID Command Name
208 4A1A set_SZFault