Variable Name: BtmBlockingDist
Variable ID: 0x4710
Variable Label: Btm Blocking Dist
Variable Help: Bottom Blocking Dist defines an area at the bottom of the vessel where reflections cannot be measured effectively due to angled bottoms, heating coils, reflections from flat metal tank bottoms in low dielectric applications, etc. It is the distance from the bottom of the tank to the lowest valid level reading. The Level reading (and mA value) will never be lower than the value related to the Bottom Blocking Distance.
Variable Handling: R/W
Variable Class:
Variable Size: 4
Variable DataType: Float
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max:
Variable Min:
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
133 | 49D9 | read_BtmBlockingDist |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
134 | 49DA | set_BtmBlockingDist |