Loading…
Loading…
Variable Name: echo_loss_fault
Variable ID: 0x4057
Variable Label: Echo Loss Fault
Variable Help: Echo Loss Fault defines how the Analog Output will respond when the transmitter detects a loss of echo exceeding the delay time. Enable fault to ensure safe, reliable high-level readings in critical applications. If Latch 3.6 or Latch 22 is chosen, the unit will remain in alarm until it is manually cleared with the SZ Alarm Reset.
Variable Handling: R/W
Variable Class: Diagnostic | AnalogOut
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | 22 mA |
0x0001 | 3.6 mA |
0x0002 | Hold |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
205 | 4119 | read_echo_loss_fault |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
206 | 411A | set_echo_loss_fault |