Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label:

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
131 4025 read_ProbeLength
133 406A read_LevelOffset
141 406C read_MeasType
145 402C read_Trim4mA
147 402D read_Trim20mA
149 406E read_UserPassword
153 4070 read_F1Polarity
155 4072 read_F1Threshold
157 4034 read_DriveAmplitude
159 4036 read_Sensitivity
161 4038 read_MagnetrolSSN
163 4074 read_CopFirmwareVersion
165 403B read_ConversionFactor
167 4075 read_ScaleOffset
169 403D read_Initials
173 4040 read_SensorMount
175 4078 read_TrimLevel
177 407A read_TrimIfcLvl
179 4042 read_FirmwareVersion
182 407C read_F2Polarity
184 407E read_F2Threshold
186 4043 read_Deadband
188 4080 read_FloatMinSep
197 4082 read_Float1Counts
198 4083 read_Float2Counts
202 4084 read_ElecTemp
203 4085 read_MaxTemp
204 4086 read_MinTemp
214 4088 read_Factory_Param1
216 408A read_Factory_Param2
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
16 00B8 read_final_assembly_number
33 0FA5 read_transmitter_variables
48 0FCE read_additional_transmitter_status
50 0FD4 read_transmitter_variable_assignments

Variable Write Command List