Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
523 1303 read_condensed_status_map
523 1303 read_condensed_status_map
523 1303 read_condensed_status_map
523 1303 read_condensed_status_map
204 45B7 rcmBe32EventsDeviceSpecificStatus
240 45DD rcmReadParameterProtection
248 45DF rcmReadSparStates
248 45DF rcmReadSparStates
248 45DF rcmReadSparStates
252 45E3 rcmReadVerificationString
252 45E3 rcmReadVerificationString
230 45E4 Command_230
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
232 45E6 Command_232
236 45E8 Command_236
140 45EB rcmFlGlobalLower
141 45ED rcmFlGlobalUpper
144 45EF rcmColFlUniGlobalLower
145 45F1 rcmColFlUniGlobalUpper
148 45F3 rcmCol2FlUniGlobalLower
152 45F5 rcmUiGlobalLower
153 45F7 rcmUiGlobalUpper
156 45F9 rcmUi16GlobalLower
157 45FB rcmUi16GlobalUpper
160 45FD rcmCol2FlGlobalLower
161 45FF rcmCol2FlGlobalUpper
164 4601 rcmStGlobalLower
164 4601 rcmStGlobalLower
164 4601 rcmStGlobalLower
165 4603 rcmStGlobalUpper
165 4603 rcmStGlobalUpper
176 4606 rcmColFlUniLocal
172 4607 rcmCgNumberLocal
174 4608 rcmElectronicSerialNumber
187 460E rcmColFlUniGdcFbOutput
188 460F rcmIdIdentnumberAndHardwareCode
189 4610 rcmIdSoftwareVersionNumber
190 4611 rcmIdProductionAndCalibrationDate
191 4612 rcmIdBoardSerialNumber
195 4614 rcmSimulationFuncitons
195 4614 rcmSimulationFuncitons
195 4614 rcmSimulationFuncitons
210 4615 rcmUi32GlobalLower
185 4617 rcmGdcAccessLevelHart
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
9 00DD read_device_variables_and_status
7 00DB read_loop_configuration
8 00DC read_dynamic_variable_classification
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
20 00DE read_long_tag
48 1043 read_additional_device_status
48 1043 read_additional_device_status
33 1054 read_device_variables
50 1052 read_device_variable_assignments
54 1057 read_device_variable_information
60 0FE5 read_analog_output_and_percent_of_range
61 0FE7 read_dynamic_variables_and_pv_analog_output
62 1062 read_analog_channels
63 104B read_analog_channel_information
70 1022 read_analog_channel_endpoint_values
110 1001 read_all_dynamic_variables

Variable Write Command List

None