Loading…
Loading…
Variable Name: device_specific_status_4
Variable ID: 0x102F
Variable Label: Status group information 1
Variable Help: Status group information 1
Variable Handling: R
Variable Class: Dynamic | Diagnostic | Device
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0080 | B2: SV >= SV switch point limit |
0x0040 | B2: PV < (PV switch point limit - PV switch point hysteresis) |
0x0020 | B2: PV >= PV switch point limit |
0x0010 | Binary output B2 (ESK4-IO module) is activated |
0x0008 | B1: SV >= SV switch point limit |
0x0004 | B1: PV < (PV switch point limit - PV switch point hysteresis) |
0x0002 | B1: PV >= PV switch point limit |
0x0001 | Binary output B1 (ESK4-IO module) is activated |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
48 | 1043 | read_additional_device_status |
Variable Write Command List
None