Loading…

Variable Name: hdeThresh

Variable ID: 0x4120

Variable Label: OF Threshold

Variable Help: Threshold value for overfill detection, related to gain V=6 (10000 corresponds to line height 2500 at V=5; 625 at V=4; 156 at V=3 etc.). If an overfilling is not recognized, the threshold value may be decreased. If the measured level jumps to the top without overfilling, the threshold value may be increased. With Fct. "BD Detect" the overfill detection can be switched off completely, too. Acceptable input range: 0 - 9999999 Default value: 10000 (SEr. 4.1.2)

Variable Handling: R/W

Variable Class: Correction

Variable Size: 4

Variable DataType: Float

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: 999999

Variable Min: 0

Variable Read Command List

None

Variable Write Command List

None