Variable Name: hdeThresh
Variable ID: 0x4120
Variable Label: OF Threshold
Variable Help: Threshold value for overfill detection, related to gain V=6 (10000 corresponds to line height 2500 at V=5; 625 at V=4; 156 at V=3 etc.). If an overfilling is not recognized, the threshold value may be decreased. If the measured level jumps to the top without overfilling, the threshold value may be increased. With Fct. "BD Detect" the overfill detection can be switched off completely, too. Acceptable input range: 0 - 9999999 Default value: 10000 (SEr. 4.1.2)
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: 999999
Variable Min: 0
Variable Read Command List
None
Variable Write Command List
None