Variable Name: flangeDist
Variable ID: 0x40B1
Variable Label: Distance piece
Variable Help: The length of any supplied distance piece above the mounting flange is factory-set here. · Setting range: 0 ... 2000 mm · Default value: 0 mm The value of 120 mm should be entered for the high-temperature version of the flange system. When a curved antenna extension is used, the horizontal component of this extension should additionally be entered (= geometric length of the pipe minus the vertical offset). (Fct. 3.1.5)
Variable Handling: R/W
Variable Class: Device
Variable Size: 2
Variable DataType: Unsigned
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
132 | 40AE | read_user_data_enums |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
133 | 40C6 | write_user_data_enums |