Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
128 4041 ReadLocationStringVariable
130 4045 ReadVersion
136 4047 ReadSerialNumber
137 405B ReadOneLowFloat
143 4069 ReadOneLowUnsignedInteger
153 406C ReadProcessEvents
147 4070 ReadOneLowString
149 4083 ReadClassifiedStatus
180 40E4 ReadLocationStringVariableSC200
182 40E9 ReadVersionsAndSNSC200
183 40EC ReadDiagnosticsSC200
186 4118 ReadOutput_1_SC200
187 4119 ReadOutput_2_SC200
189 415B ReadOneLowFloatSC200
191 41AC ReadLowUnsignedIntegerSC200
192 41AD ReadRelayA_1_SC200
193 41AE ReadRelayA_2_SC200
194 41AF ReadRelayB_1_SC200
195 41B0 ReadRelayB_2_SC200
196 41B1 ReadRelayC_1_SC200
197 41B2 ReadRelayC_2_SC200
198 41B3 ReadRelayD_1_SC200
199 41B4 ReadRelayD_2_SC200
201 41CB ReadHighFloatSC200_1
202 41CC ReadHighFloatSC200_2
204 41F2 ReadHighUnsignedIntegerSC200
205 41F6 ReadOneLowUnsignedLongIntegerSC200
206 4204 ReadHighUnsignedLongIntegerSC200
207 4207 ReadLowStringVariableSC200
220 4270 ReadAnalogChannelsHART
176 429E ReadHARTOutputLoopA
177 429F ReadHARTOutputLoopsB
178 42A0 ReadHARTOutputLoopC
170 42A5 ReadDeviceMappingVariableHARTModule
171 42A6 ReadLocationStringVariableHARTModule
173 42A8 ReadVersionsAndSNHARTModule
208 42AA ReadDate
210 42AD ReadTime
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
9 00DD read_device_variables_and_status
7 00DB read_loop_configuration
8 00DC read_dynamic_variable_classification
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
20 00DE read_long_tag
48 1043 read_additional_device_status
48 1043 read_additional_device_status
50 1052 read_device_variable_assignments

Variable Write Command List

None