Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
128 402D ReadLocationStringVariables
130 4031 ReadVersion
136 4033 ReadSerialNumber
137 4045 ReadOneLowFloat
143 404B ReadOneLowUnsignedInteger
153 404E iReadProcessEvents
147 4052 ReadOneLowString
149 4065 ReadClassifiedStatus
220 40C7 ReadAnalogChannelsHART
176 40F7 ReadHARTOutputLoopA
177 40F8 ReadHARTOutputLoopsB
178 40F9 ReadHARTOutputLoopC
170 4102 ReadDeviceMappingVariableHARTModule
171 4103 ReadLocationStringVariableHARTModule
173 4105 ReadVersionsAndSNHARTModule
208 4107 ReadDate
210 410A ReadTime
180 413B ReadLocationStringVariableSC200
182 4140 ReadVersionsAndSNSC200
183 4143 ReadDiagnosticsSC200
186 416D ReadOutput_1_SC200
187 416E ReadOutput_2_SC200
189 41AC ReadOneLowFloatSC200
191 41FD ReadLowUnsignedIntegerSC200
192 41FE ReadRelayA_1_SC200
193 41FF ReadRelayA_2_SC200
194 4200 ReadRelayB_1_SC200
195 4201 ReadRelayB_2_SC200
196 4202 ReadRelayC_1_SC200
197 4203 ReadRelayC_2_SC200
198 4204 ReadRelayD_1_SC200
199 4205 ReadRelayD_2_SC200
201 421C ReadHighFloatSC200_1
202 421D ReadHighFloatSC200_2
204 4243 ReadHighUnsignedIntegerSC200
205 4247 ReadOneLowUnsignedLongIntegerSC200
206 4255 ReadHighUnsignedLongIntegerSC200
207 4258 ReadLowStringVariableSC200
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
9 00DD read_device_variables_and_status
7 00DB read_loop_configuration
8 00DC read_dynamic_variable_classification
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
20 00DE read_long_tag
48 1043 read_additional_device_status
48 1043 read_additional_device_status
50 1052 read_device_variable_assignments

Variable Write Command List

None