Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
128 4027 ReadLocationStringVariable
130 402B ReadVersion
136 402D ReadSerialNumber
137 403C ReadOneLowFloat
139 4041 ReadOneLowInteger
143 404B ReadOneLowUnsignedInteger
145 4050 ReadOneLowUnsignedLongInteger
153 4052 ReadProcessEvents
149 4064 ReadClassifiedStatus
180 409A ReadLocationStringVariableSC200
182 409F ReadVersionsAndSNSC200
183 40A2 ReadDiagnosticsSC200
186 40CE ReadOutput_1_SC200
187 40CF ReadOutput_2_SC200
189 4111 ReadOneLowFloatSC200
191 4162 ReadLowUnsignedIntegerSC200
192 4163 ReadRelayA_1_SC200
193 4164 ReadRelayA_2_SC200
194 4165 ReadRelayB_1_SC200
195 4166 ReadRelayB_2_SC200
196 4167 ReadRelayC_1_SC200
197 4168 ReadRelayC_2_SC200
198 4169 ReadRelayD_1_SC200
199 416A ReadRelayD_2_SC200
201 4181 ReadHighFloatSC200_1
202 4182 ReadHighFloatSC200_2
204 41A8 ReadHighUnsignedIntegerSC200
205 41AC ReadOneLowUnsignedLongIntegerSC200
206 41BA ReadHighUnsignedLongIntegerSC200
207 41BD ReadLowStringVariableSC200
220 4226 ReadAnalogChannelsHART
176 4254 ReadHARTOutputLoopA
177 4255 ReadHARTOutputLoopsB
178 4256 ReadHARTOutputLoopC
170 425B ReadDeviceMappingVariableHARTModule
171 425C ReadLocationStringVariableHARTModule
173 425E ReadVersionsAndSNHARTModule
208 4260 ReadDate
210 4263 ReadTime
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
9 00DD read_device_variables_and_status
7 00DB read_loop_configuration
8 00DC read_dynamic_variable_classification
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
20 00DE read_long_tag
48 1043 read_additional_device_status
48 1043 read_additional_device_status
50 1052 read_device_variable_assignments

Variable Write Command List

None