Loading…
Loading…
Variable Name: fLowSignal
Variable ID: 0x401F
Variable Label: Low Signal
Variable Help: Low Input Signal- Lower range value of input signal for valve closed (direct acting) or lower range value of input signal for valve open (reverse acting). Must be between 3.8 mA and 14 mA.
Variable Handling: R/W
Variable Class: Correction
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.2f
Variable Edit Format: |en|5.2f
Variable Unit:
Variable Max: 14
Variable Min: 3.8
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
213 | 4183 | cmdReadSignalValues |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
181 | 4170 | cmdWriteSignalValues |