Loading…
Loading…
Variable Name: Digit_Data_Point
Variable ID: 0x400B
Variable Label: Digit DP
Variable Help: XMTR LCD- Transmitter LCD display parameter. XMTR LCD Display is able to set in independence with Analog Output. Digit DP: Digit under Decimal Point- Available range is from 0 to 4 as below; 0 (XXXXX) 1 (XXXX.X) 2 (XXX.XX) 3 (XX.XXX) 4 (X.XXXX)
Variable Handling: R/W
Variable Class: Device
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
193 | 4081 | read_lcd_indication_coefficient_193 |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
194 | 4082 | write_lcd_indication_coefficient_194 |