Variable Name: flowCalc
Variable ID: 0x4017
Variable Label: Flowrate calculate pulses
Variable Help: The flowrate is calculated by measuring the time between a number of pulses, for example 10 pulses. The more pulses the more accurate the flowrate will be. The maximum value is 255 pulses. Note: the lower the number of pulses, the higher the power consumption of the unit will be (important for battery powered applications). Note: for low frequency applications (below 10Hz): do not program more than 10 pulses else the update time will be very slow. Note: for high frequency application (above 1kHz) do program a value of 100 or more pulses.
Variable Handling: R/W
Variable Class:
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format: |en|3d
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
130 | 4019 | readFlowratePulseConfig |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
131 | 401B | writeFlowratePulseConfig |